| Advanced data for product |
| Nominal voltage |
| Specific value | 24 VDC |
| Limit values, min/max | 14/30 VDC |
| Nominal current, typically |
| Specific value | 50 mA |
| Condition | unloaded |
| Device design |
| Type | Single-/Multi-Turn |
| Total resolution | <= 24 Bit |
| Number of steps per revolution | <= 4096 |
| Number of revolutions | <= 4096 |
| Accuracy | ± 1.0 ° |
| Analog - Interface |
| Voltage/Current | programmable |
| Resolution 12 Bit D/A converter |
|
| Resolution | 16 Bit D/A converter, optional |
| Voltage output | 0…+10 VDC |
| Load resistance (U) | >= 20 kOhm |
| Current output | 0…24 mA |
| Load resistance (I) | <= 350 Ohm |
| Cycle time | 500 µs |
| Parameter/Function, changeable | Resolution |
| | Analog Voltage/Current |
| | Preset parameter |
| | Counting direction |
| Type of parametrization | programmable |
| Programming - Tool | TR-Soft: TRWinProg |
| External inputs |
| Function input | Count direction or Preset |
| Type of parametrization | programmable |
| Logic level | "0“ < +2V, "1“ = Supply |
| Maximum Speed, mechanically | <= 10000 1/min |
| Shaft load, axial/radial | <= 10 N, <= 5 N |
| Bearing life time | >= 30E+9 revolutions |
| Bearing life time - Parameter |
| Speed | 3000 1/min |
| Operating temperature | <= 25 °C |
| Shaft load, axial/radial | <= 5 N, <= 2,5 N |
| Point of origin, shaft load | at the shaft end |
| Shaft type |
| Shaft diameter [mm] | 6 |
| Shaft diameter ["] | 1/4 |
| General environmental conditions |
| Vibration |
| Specific value | <= 100 m/s² |
| Sine | 50…2000 Hz |
| Shock |
| Specific value | <= 1000 m/s² |
| Half sine | 11 ms |
| Immunity to disturbance | DIN EN 61000-6-2 |
| Transient emissions | DIN EN 61000-6-3 |
| Working temperature |
| Standard | 0…+60 °C |
| Storage temperature, dry | 0…+85 °C |
| Relative humidity | 95 %, non condensing |
| Protection class |
| Standard | IP64 |